Technical Guide Guida all’installazione
The manifold is the heart of any underfloor heating system. Get the installation and flow balancing right and the floor heats evenly for decades; get it wrong and the fault is buried under the screed. Here is the whole job — parts, six installation steps, flow-meter balancing, actuator and thermostat wiring — plus the mistakes that cause callbacks.
The manifold splits one supply into multiple floor loops, controls the flow to each one, and carries the actuators that switch zones on and off. Get the manifold installation and flow balancing right and the floor heats evenly, runs efficiently, and never gets touched again. Get it wrong and you have cold spots, wasted energy, or worse — a leak buried under the screed. This guide walks an installer through the whole job: the manifold parts, the step-by-step installation, balancing the loops with flow meters, and wiring the actuators to the thermostat — plus the common mistakes that cause callbacks.
It is written for the people who actually handle the system: plumbing and heating installers fitting a manifold on site, distributors who need an install reference to hand their customers, and project buyers confirming a system can be commissioned cleanly. The steps are general good practice for any quality manifold; where a value would be a manufacturer-specific spec, always confirm it against the product datasheet before you commission. Underfloor heating is a premium, high-margin system — installing it right is what turns a first order into a reorder. For the hardware itself, see the WARMHAUS brass manifold range and the wider underfloor heating system.
Before installing anything, know what each part does — most balancing and wiring mistakes come from not reading the manifold correctly. A typical manifold is two horizontal bars, usually brass, mounted one above the other:
| Part | What it does |
|---|---|
| Flow bar | The top bar; feeds heated water out to each loop. Carries the flow meters. |
| Return bar | The bottom bar; collects cooled water back from each loop. Carries the actuator valves. |
| Flow meters (flow gauges) | One per loop on the flow bar. Set and display each loop’s flow rate — the tool you balance with. |
| Actuator valves | One per loop on the return bar. The electrothermal actuator screws on here to open or close the loop on thermostat demand. |
| Isolation valves | Shut off the whole manifold from the supply and return for service without draining the system. |
| Air vents / drain-fill valves | At the manifold ends; purge trapped air and fill or drain loops during commissioning. |
| Temperature gauges | Show flow and return temperature so you can confirm the floor is running in the safe range. |
| Pump / mixing group (if fitted) | Blends hot boiler water down to a floor-safe temperature and circulates it through the loops. |
The number of ports tells you the number of loops — a 2-to-8-port manifold serves 2 to 8 heating circuits, and larger jobs gang manifolds together. The key thing for installation: the flow meters live on the flow bar (balancing), the actuators live on the return bar (control) — mix those up and nothing works as intended. See the WARMHAUS manifold range (2–8 ports) with built-in flow meters.
These six steps are the standard sequence for a clean, testable install. Follow them in order — the order is what keeps you from burying a fault under concrete.
Fix the manifold to a wall or into a manifold cabinet, above the finished floor level, and use a spirit level so both bars sit perfectly horizontal. Level matters: a tilted manifold traps air in the high loops and skews your flow readings. Leave clearance below for the loop bends coming up out of the floor and above for the actuators and wiring.
Bring the flow and return from the heat source to the manifold isolation valves, keeping flow to the flow bar, return to the return bar. If the system uses a pump/mixing group or a thermostatic blending valve to protect the screed from over-temperature water, fit it here between the heat source and the manifold.
Cut each oxygen-barrier PEX-B loop square, push in the pipe support sleeve, and connect it to the manifold outlet with a compression or Euro-cone insert fitting — hand-tight, then wrench to the fitting’s spec, no more. Number every loop and write down its length. You will need those lengths to balance flow in Step V. For the pipe side of the job, see WARMHAUS PEX-B pipe.
Fill the system, then purge air one loop at a time through the drain valves until each runs clear. Pressure-test to the required test pressure and hold — before any screed is poured. This is the single most important step in the whole job. Leave the loops under pressure during the screed pour so any damage shows up immediately.
A leak found now is a fitting re-seated in five minutes; a leak found after the pour is a broken floor.
With the pump running and the floor filled, adjust each loop’s flow meter so its flow rate matches its loop length — covered in detail in the next section. Balancing is what makes the whole floor heat evenly.
Screw an electrothermal actuator onto each return-bar valve, then wire the actuators and room thermostats — covered after the balancing section. Commission the system, confirm each zone opens on demand, and hand over.
Want this as a one-page site reference? Download the full Installation PDF — six-step install diagram, balancing quick-reference table and the common-mistakes checklist — or go straight to the WARMHAUS underfloor heating manifold.
Balancing is the step that separates a floor that heats evenly from one with cold corners — and it is the step installers most often skip. The idea is simple: water is lazy and takes the easy path. Left alone, most of the flow rushes through the short loops and starves the long ones, so part of the floor is warm and part stays cold. The flow meters let you force fair shares.
Design, Not Guesswork Il progetto
Target flow rates per loop depend on loop length, spacing, floor construction and design heat load — they come from the system design, not from a rule of thumb, so work to the project’s loop schedule where one exists. A properly balanced manifold means even floor temperature, lower return temperatures, and a system that runs quietly and efficiently for decades.
Every WARMHAUS manifold ships with flow meters built in, so balancing is a read-and-set job — no blind guessing at lockshield turns.
See WARMHAUS manifolds with built-in flow metersThe pipework moves heat; the controls decide when and where. This is the electrical side of the manifold, and it is what makes underfloor heating a zoned, room-by-room system instead of one big warm slab.
Note that most electrothermal actuators are “normally closed” — they need power to open — so nothing heats until a thermostat calls, which is exactly the fail-safe behaviour you want. Match the actuator voltage (commonly 24 V or 230 V) and the thermostat type to the system design; confirm the exact rating against the product datasheet before wiring. See WARMHAUS actuators & thermostats for the matched control side of the system.
Avoid the Callbacks Gli errori comuni
Almost every underfloor heating callback traces back to one of these. Check them off before you commission.
The costliest mistake there is. Always test and hold pressure before the pour — and keep the loops pressurised during it. (See Step IV.)
An unbalanced manifold gives warm and cold patches on the same floor. Set every flow meter to its loop length; do not leave them all wide open. (See the balancing section.)
Trapped air blocks a loop so it never heats. Bleed each loop individually at fill, and again after first firing.
A tilted manifold traps air and throws off flow readings. Level both bars with a spirit level.
Flow meters go on the flow bar (balancing); actuators go on the return bar (control). Swapping them means nothing controls correctly.
Hand-tight then to spec — cranking a compression fitting past its spec can crack it and cause the exact buried leak you are trying to avoid.
Underfloor loops run at a lower temperature than radiators; use the mixing/pump group or blending valve so you do not stress the screed and pipe.
A manifold only installs cleanly when the parts are made to match — the pipe fits the fitting, the actuator fits the valve, the thermostat speaks to the wiring centre. That is the case for sourcing the whole system from one manufacturer. WARMHAUS builds the complete underfloor heating system — oxygen-barrier PEX-B pipe, brass manifolds with built-in flow meters, and electrothermal actuators and thermostats — as part of a 270+ SKU piping range. Made in Italy in Bologna since 1970, ISO 9001 / ISO 14001 / SKZ / DVGW certified. One matched, certified system for installers, distributors, projects and private-label partners. MOQ, lead times, pricing and exact certificate numbers: available on request — small trial orders welcome.
FAQ Domande frequenti
Start Here Parliamone
Tell us your market and the systems you install or sell, and we will send specifications, certifications and distributor terms. Small trial orders welcome. Response time: Coming soon.